Contact
France

Online remediation of a cooling water circuit

Removal of hydrocarbons from the cooling water circuit by means of de-oiling and filtering
Download PDF

Online remediation of a cooling water circuit

France

The cooling water system of a power generation site had become contaminated with hydrocarbon pollution.

This circuit, with a volume of 180 m3 (234 yd3), had a total oil and grease concentration of 320 mg/l with a maximum target of 10 mg/l, i.e. a target decrease of 97 %. The objective was to intervene effectively on this circuit without stopping production.

CTP environnement's solution consisted of diverting a fraction of the flow to a temporary treatment plant, then reinjecting the treated water into the refrigeration circuit.

The diverted flow, of the order of 1 m3/h (4,4 gpm), is insignificant for cooling; this meant the operation was possible without disruption to the system.

image

The temporary treatment system deployed by CTP environnement consisted of an oil separator, a bag filtration stage, and a finalising stage on activated carbon.

This system allows a widespread reduction of the total, soluble and insoluble, oils and grease.

The installation, fully automated and secure, also allowed an exceptionally economical and continuous 24h/24, 7d/7 treatment.

image

Key project figures :

News
27th January 2026
Carrefour des Gestions Locales de l'Eau 2026

We exhibited on 21 and 22 January at the Carrefour des Gestions Locales de l’Eau in Rennes, which has been bringing together all public and private stakeholders in the water sector for over 25 years.